Features
- Depth: 120mm (incl. hinges 150mm).
- Width: 600mm, 700mm, 800mm (DCD50 only available for 800mm).
- Cooling capacity: up to 50kW (suited for sensitive cooling only).
- Air pressure loss: 35Pa (at 4,900m³/h) for DCD 35 / 30Pa (at 6500m³/h) for DCD50.
- Water pressure loss: 54kPa (at 5m³/h) for DCD35 / 68kPa (at 7.2kW) for DCD50.
- Chilled water supply: 15°C.
- Chilled water return: 21°C.
- Server supply air temperature: 25°C @35kW for DCD35; @50kW for DCD50.
- Chilled water volume flow: 5m³/h at 35kW / 7.2m³/h at 50kW.
- Water connection: 1“ female thread from below (optionally from above).
- Condensate drain: 5/8“ (Note: Not for dehumidifying the installation area!).
- Absolute humidity/ room air: max. 8g water per 1 kg of air (others on request).
- Dew-point temperature: max. 10.5°C.
- Material: Sheet steel.
- Heat exchanger: Copper piping with aluminum lamellas.
- Color/color code: X: 8 = RAL 7021 (black gray) / 1 = RAL 7035 (light gray).
BENEFITS
- Improved PUE.
- Suggested to be used in a cold-room concept.
- Low pressure loss.
- No fans.
- Increased chilled water supply temperature.
- Reliable operation guaranteed by water-conducting hinges.